KE switch cabinet module
4 inputs (PNP) and 3relay outputs

General specifications

Slave typeA/B slave
AS-Interface specificationV2.1
Required master specification? V2.1
UL File NumberE106378

Functional safety related parameters

MTTFd330 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %

Indicators/operating means

LED FAULTFault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
LED INTInternal input supply active; LED green
LED PWRAS-Interface voltage; LED green
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 3 LED yellow

Electrical specifications

Auxiliary voltage (input)12 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current? 35 mA (without sensors) / max. 235 mA
Surge protectionO1 ... O3: Over voltage category II
UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV)

Input

Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage21 ... 31 V DC (INT)
Current loading capacity? 150 mA, overload- and short-circuit protected (INT)
Input current? 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
Signal delay< 2 ms (input/AS-Interface)
Signal frequency? 250 Hz

Output

Number/Type3 relay outputs, normally open
Supplynone
Nominal load
Minimum load
Short-circuit-proofContact: 500 A / 40 ms
Switching off power500 VA
Switching delay< 10 ms (AS-Interface/contact)
Usage categoryDC-13 and AC-14
Switching frequency< 20 Hz (without load)
< 0.1 Hz (nominal load)
Switching

Galvanic isolation

Input/OutputIN1 ... IN4 to O1 ... O3: safe isolation acc. to EN 60947-1,
rated insulation voltage 278 V AC
Input/AS-Interfacenone
Output/OutputO1 to O2, O3: safe isolation according to EN 60947-1,
rated insulation voltage 278 V AC
O2 to O3: basic insulation according to EN 60947-1,
rated insulation voltage 278 V AC
Output/AS-Interfacesafe isolation acc. to EN 60947-1,
rated insulation voltage 278 V AC

Directive conformity

Electromagnetic compatibility
Low voltage

Standard conformity

Galvanic isolationEN 60947-1
Electromagnetic compatibilityNAMUR NE 21: 1998-08
Degree of protectionEN60529:2000
Pollution degree