AS-Interface sensor/actuator module VAA-4E4A-KE5-ZEJQ/R - фото 1 - id-p95198874
Характеристики и описание

Техническая спецификация в PDF  

Описание оборудования

Cabinet module
4 inputs and 4 relay outputs

General specifications

Slave typeStandard slave
AS-Interface specificationV3.0
Required master specification? V2.0
UL File NumberE223772
MTBF224 a

Indicators/operating means

LED FAULTFault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
LED INTInternal input supply active; LED green
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 4 LED yellow

Electrical specifications

Auxiliary voltage (input)12 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current? 35 mA (without sensors) / max. 230 mA
Surge protectionO1 ... O4: Over voltage category II
UEXT, Ue: overvoltage category II, safe isolated power supplies (PELV)

Input

Number/Type4 inputs for 3-wire sensors (PNP), DC
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage21 ... 31 V DC (INT)
Current loading capacity? 150 mA, overload- and short-circuit protected (INT)
Input current? 5.6 mA (max.)
Switching pointaccording to DIN EN 61131-2 (type 1)
Signal delay< 1 ms (input/AS-Interface)

Output

Number/Type4 relay outputs, normally open
Supplynone
Nominal load
Control circuit? 11 mA per relay (from AS-Interface)
Switching delay< 10 ms (AS-Interface/contact)
Usage categoryDC-13 and AC-14
Switching

Galvanic isolation

Input/Outputsafe isolation, Rated insulation voltage252Veff
Input/AS-InterfaceSwitch position INT: None Switch setting EXT: safe isolation, rated insulation voltage 92Veff
Output/OutputBasic insulation, rated insulation voltage 250Veff, in phase
Output/AS-Interfacesafe isolation, Rated insulation voltage252Veff

Directive conformity

Electromagnetic compatibility
Low voltage

Standard conformity

Galvanic isolationEN 60664-1:2007
Degree of protectionEN60529:2000
Fieldbus standardEN62026-2:2013
Electrical safetyIEC61140:2009
InputEN 61131-2:2004
Emitted interferenceEN61000-6-4:2007
AS-InterfaceEN62026-2:2013
Noise immunityEN61000-6-2:2005, EN61326-1:2006, EN62026:2013

Programming instructions

ProfileS-7.0
IO code7