G2 flat module
4 inputs (PNP) and 4electronic outputs

General specifications

Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification? V3.0
UL File NumberE223772

Functional safety related parameters

MTTFd140 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %

Indicators/operating means

LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or outputs
LED PWRAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 4 LED yellow

Electrical specifications

Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current? 40 mA (without sensors) / max. 220 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)

Input

Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
option 2 inputs for 4-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity? 180 mA (TB ? 40 °C),
? 140 mA (TB ? 60 °C), , overload and short-circuit protected
Input current? 9 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
Signal delay< 2 ms (input/AS-Interface)
Signal frequency? 250 Hz

Output

Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Current0.5 A per output , 2 A total
Voltage? (UAUX - 0.5 V)

Directive conformity

Electromagnetic compatibility

Standard conformity

Degree of protectionEN60529:2000
Fieldbus standardEN62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN61000-6-4:2001
AS-InterfaceEN62026-2:2013
Noise immunityEN61000-6-2:2001

Programming instructions

ProfileS-7.A.7
IO code7
ID codeA
ID1 code7
ID2 code7
Data bits (function via AS-Interface) input output
Parameter bits (programmable via AS-i)function

Ambient conditions