Technical data | ELX3202 |
---|
Technology | temperature measurement |
Sensor types | PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (10 Ω…4 kΩ), KT(Y) sensors |
Number of inputs | 2 (differential) |
Connection method | 2-, 3-, 4-wire (default: 2-wire) |
Temperature range | -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors), for further types and details see documentation |
Resolution | 0.1 °C per digit |
Measuring current | < 1="" ma="" (depending="" on="" sensor="" and="" measuring=""> |
Measuring error | < ±0.3="" %="" (relative="" to="" full="" scale=""> |
Internal resistance | typ. ≥ 10 kΩ (differential) |
Input filter limit frequency | typ. 1 kHz |
Conversion time | 10…3300 ms (adjustable, default: 170 ms) |
Supply voltage electronics | 24 V DC (via power contacts), ELX9560 power supply |
Current consumption power contacts | typ. 10 mA |
Current consumption E-bus | typ. 70 mA |
Special features | limit value monitoring, digital filter and characteristic curve linearisation integrated, connection method freely configurable |
Weight | approx. 60 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/see documentation |
Approvals/Markings | CE, ATEX, IECEx |
Ex-Marking | II 3(Или отправьте нам запрос наII (1)D [Ex ia Da] IIICI (M1) [Ex ia Ma] IEx ec [ia Ga] IIC T4 Gc[Ex ia Da] IIIC[Ex ia Ma] I |